8.7/15kv Cold Shrink Cable Indoor Outdoor Joint Terminal Kit

US$85.00 50 Sets (MOQ)
Port:
Shanghai, China
Production Capacity:
500000 Sets/Year
Payment Terms:
L/C, T/T, D/P, Western Union, Paypal, Money Gram

Last Login Date:

Jul 20, 2023

Business Type:

Manufacturer/Factory, Trading Company

Main Products:

Heat Shrinkable Sleeve for Pipes, Heat Shink Tube, Heat Shrink End Cap, Medium Wall Heat Shrink Tube, Heat Shrink Termination Kit, Cold Applied Wrap Tape, Heat Shrink Tubular Sleeve, Heat Shrink Sleeve for Busbar

Find Similar Products

Product Description

Company Info

Basic Info.

Model NO.
BHST
Certification
CCC, RoHS, ISO
Color
Grey
IP Rating
IP68
Usage
Optical Cable, Lighting Decoration, Earphone Line, Electric Wire, DVI Line, HDMI Cable
Material
Rubber
Type
Cold Shrink
Voltage
8.7-15kv
Core Quantity
3 Cores
Cable Section Area
25-630mm2
Key Word
Termination Kit
Trademark
CJDS
Transport Package
Packing in Carton
Specification
25mm2 to 630mm2
Origin
China
HS Code
8547200000

Product Description

8.7/15KV cold shrink cable indoor outdoor joint terminal kit
Product facts:
The cable terminal is one-piece design manufactured from high quality liquid silicone rubber. The cold shrink terminal is factory
expanded on a removable inner-supporting core. Once the terminal is positioned onto the cable core, the supporting core is unwound
and removed, and the live-memory action of the material shrinks the terminal into place. The terminal kit includes all the
necessary components to make the installation.
- Material:silicone rubber
- Nominal voltage:8.7/15KV
- Allowable highest continuous operating voltage: 17.5KV
- Type: indoor/outdoor
- Cores number:1 core/3 cores
-Transmission capacity: consistent with the cable
 
Product features/benefits:
- Simple and fast Product facts:, no heat or special tools required.

- One-piece design with integrated stress control.

- Offering protection against aging, tracking and erosion.

- High resistance to fungus, acid, alkalis and ozone.

- Accommodating a wide range of cable sizes: 25~630 sqmm.
 
Test itemStandardTest result
Power frequency withstand voltage testunder 45kv, within 1min. no flash and no breakdownunder 45kv, within 1min. no flash and no breakdownQualified
Partial discharge testThe magnitude of discharge at 13KV shall not exceed 20pC.The magnitude of discharge of combination samples is 3pc at 13KV.Qualified
Heating cycles voltage test for 3 weeksHeated for 5 hours, cooled for 3 hours, and the conductor temperature is 95ºC while heating.Decided by the following 4 test results.
Partial discharge testThe magnitude of discharge at 13KV shall not exceed 20pC.The magnitude of discharge of combination samples is 3pc at 13KV.Qualified
Impulse withstand voltage testNo breakdown shall occur at 10 positive and 10 negative impulses of 105KV.No breakdown occured on the combination samples at 10 positive and 10 negative impulses of 105KV.Qualified
Negative polarity DC withstand voltage testNo breakdown shall occur at 52KV for 15min.No breakdown occured on the combination samples at 52KV for 15min.Qualified
Power frequency withstand voltage test for 4 hourssNo breakdown shall occur at 35KV for 4 hours.No breakdown occured on the combination samples at 35KV for 4 hours.Qualified